High Voltage Test Set PGK 150 / 5 HB

作者:凱迪正大股份來源:武漢凱迪正大電氣有限公司日期:2015-09-12 09:29:00閱讀:

The two -part test sets PGK HB generate variable AC test voltages of mains frequency or DC voltages of positive or negative polarity.

 

The operating unit in 19“ design has a voltage and current display, safety control elements according to VDE 0104 and a variable transformer for voltage adjustment.

 

The high voltage unit contains an oil insulated high voltage transformer and, depending on the desired operation mode, a rectifier rod or a resistor rod. The polarity of the DC test voltage can be changed by reversing the rectifier in the high voltage unit.

 

Features:

 

·absolutely  maintenance-free  design

 

· stepless adjustable output voltage

 

· safety control according to VDE 0104

 

· short-circuit protected by internal current limitation

 

· voltage indication: 2 range analogue meter, ratio 1:3

 

· current measurement: 3 range analogue meter, decadic

 

· thermal overcurrent switch-off

 

Technical data

 

 

PGK 150 / 5 HB

Mains supply

220 - 240 V

 

110 - 120 V with external

 

autotransformer

Mains frequency

45 Hz up to 60 Hz

Power consumption

 

5750 VA

Power consumption short-circuit

11700 VA

Nominal output voltage AC rms / DC

110 kV / 150 kV

Output current cont. AC rms / DC

50 mA / 18 mA

Short-circuit current AC rms / DC

108 mA / 77 mA

Relative humidity

not condensing

Ambient temperature

working:

0 ... + 45 ° C

 

storage:

- 20 ... + 60 ° C

Precision of the kV-meter

 

2,5 %

Precision of the mA-meter

 

2,5 %

Dimensions control unit housing (W x H x D)

502 x 580 x 480 mm

Dimensions High Voltage part (height / diameter)

1530 mm / 640 mm

Weight control unit

 

51 kg

Weight High Voltage unit

 

180 kg